General specifications
|
Number of protected signal lines
|
1
|
Functional safety related parameters
|
Safety Integrity Level (SIL)
|
SIL 3
|
Supply
|
Rated voltage
|
≤ 48 V
|
Rated current
|
≤ 250 mA
|
Leakage current
|
≤ 5 μA
|
On-state voltage
|
≤ 85 V
|
Ground insulation
|
≥ 500 V breakdown voltage
|
Electrical specifications
|
Total discharge current (8/20 μs)
|
20 kA
|
Conformity
|
Degree of protection
|
IEC 60529:2001
|
Ambient conditions
|
Ambient temperature
|
-30 ... 60 °C (-22 ... 140 °F) For usage in hazardous area observe EC-type examination certificate.
|
Mechanical specifications
|
Housing material
|
Stainless steel 1.4401 (AISI 316)
surface all over polished
|
Degree of protection
|
IP67
|
Cable
|
|
|
Length
|
0.3 m
|
Mass
|
approx. 200 g
|
Dimensions
|
AF22 x 77 mm (0.9 x 3 inch)
|
Mounting
|
M20 x 1.5 thread
|
Data for application in connection with hazardous areas
|
EU-type examination certificate
|
PTB 00 ATEX 2175
|
|
Marking
|
II 2G EEx ia IIC T6
|
|
Voltage
|
50 V
|
Maximum leakage current
|
10 kA line to ground (common), 5 kA line to line (differential) in accordance to IEC 60-2
|
Nominal response time
|
|
|
Symmetrical
|
1 ns
|
|
Asymmetric
|
100 ns
|
Bandwidth
|
≥ 40 kHz
|
Directive conformity
|
|
|
Directive 2014/34/EU
|
EN 60079-0:2012+A11:2013 , EN 60079-11:2012
|